Service hotline:021-63027237-8001
产品分类
product
Home EnglishProductBurner Controls LDU...Burner Controls
LDU...Burner Controls

● The LDU11 is designed for automatic gas valve proving (leakage test)

    based on the  pressure proving principle.

It is for use on gas-fired combustion plant with or without vent  pipe to 

   atmosphere

● Standards and certificates


2127

Product features
Specification parameters
Data download
  • Product features

    ● Remote reset

    ● The automatic trigger time of the program is optional


  • Specification parameters

    ● Mains voltage: AC 230V, -15%/+10% 

                               AC 115V,-15%/+10%

    ● Power consumption : 3.5VA

    ● Safety class II.

    ● Degree of protection IP40 

    ● Perm. input current at terminal 1 Max. 5 A

    ● Environmental conditions Operation DIN EN 60721-3-3

                                                 Climatic conditions Class 3K5

                                                 Mechanical conditions Class 3M2

                                                 Temperature range -20...+60°C

                                                 Humidity <95%r.F.

    ● Weight: about 1000g

    ● Life cycle: LDU11 has a designed lifetime* of 250,000 burner startup cycles which


  • Data download
Service hotline:021-63027237-8001
E-mail:jinghesh2021@163.com
Office Address:Building 5, No. 1358 Jiangyue Road, Minhang District, Shanghai
Copyright © Copyright Shanghai Jinghe Thermal Energy Equipment Co., Ltd Shanghai ICP Preparation No. 2021023415-1